11 Electrical checks of
main parts
463
SMGB0087 rev.0 - 12/2013
11
11.4  High pressure protection device
If the discharge pressure is excessively high the compressor and the component parts of the refrigeration cycle can be
damaged.
High Pressure Switch (PSH):
If the discharge pressure is excessively high the compressor and the component parts of the refrigeration cycle can be da-
maged. Therefore, in case that the discharge pressure is higher than 4.15 MPa (R410A) the protection control is activated
and the compressor is stopped.
Pressure Switch for Control (PSC):
In case that the discharge pressure is higher than 3.6 MPa (R410A) the protection control might be performed.
Depending on model (check refrigerant cycle):
1  For controlling the high pressure not to increase excessively during heating operation the gas by-pass circuit and the
air volume of the outdoor fan is controlled automatically.
2  The gas by-pass circuit which is composed of the solenoid valve and the capillary tube for ow adjustment control the
high pressure not to increase excessively by leading the high pressure gas to the low pressure side.
1. Gas by-pass circuit.
2. Capillary tube.
3. Solenoid valve.
1
2
3
RAS-(2-2.5)HVNP1 / RAS-3HVNC1
High pressure
switch
Pressure switch
for control
Brazing
RAS-3HVNP1E RAS-(4-6)H(V)NP1E
Upper Cover
Discharge Pipe
Brazing
Part
Brazing Part
Low Pressure Switch
(PSL)
Suction Pipe
High Pressure Switch
(PSH)
Pressure Sensor
for PD Control
Electrical Box
Discharge pipe
Electrical Box
Upper
cover
High pressure switch
Pressure sensor for
PD control
Brazing
part
Low pressure
switch
Suction
pipe
Brazing part
Discharge Pipe
Brazing Part
Brazing Part
Brazing Part
Low Pressure Switch (PSL)
Suction Pipe
High Pressure Switch (PSH)
Pressure Sensor for PD Control
to DRM1 and SC terminals.
or transmission wiring
Do not connect power supply
17E26270A
CAUTION
SCAS4755 DRM1
PCN1
TR1
IC1
SEG1
1 62 5
ON
3 4
1
ON
2 43
1 62 5
ON
3 41 62 5
ON
3 4
ON
21
ON
21
PSW1
PSW3
0
9
8
7
6
5
4
3
2
1
SW1
DSW3
R195
REG1
E
Y20C
Y20A
Y21
Y52C
YCH
Y21SW1
Y21SW2-1
Y21SW2-2
LED3
LED2
PSW2
DSW6
RSW1
DSW1
DSW5
DSW2 DSW4
LED4
LED1
EFS1
EFR1
EF1
EF2
EF3
THM9THM10 THM7THM8
CN100
CN1 CN6 CN7
CN101
CN404
CN2
CN8CN5A
CN405 CN406
CN10
PCN9
TP1
SK1
PCN10PCN14 PCN13
PCN406
PCN8 PCN6
PCN100
PCN7 PCN5
+
C72
+
C71
DM1
+
C87
L1 1 2
L2
N
CAUTION
Discharge pipe
High pressure switch
Pressure sensor for PD control
Low pressure switch
Suction pipe
Brazing part
Brazing part
Brazing part