8 Troubleshooting
305
SMGB0087 rev.0 - 12/2013
8
9  Check items [1] – [8].
10  Touch [+] side of the tester to DIP-IPM DCL2 terminal,
and [-] side to [P] of ISPM/DIP-IPM (soldered part) to
measure the resistance. Normal if all three terminals
have 100 kΩ or greater
11  Contrary to [10], touch [-] side of the tester to DIP-
IPM DCL2 terminal, and [+] side to [P] of DIP-IPM
(soldered part) to measure the resistance. Normal if
all three terminals have 1 kΩ or greater.
12  Touch [+] side of the tester to DIP-IPM DCL2 terminal,
and [-] side to [N] of DIP-IPM (soldered part) to meas-
ure the resistance. Normal if all three terminals have
100 kΩ or greater.
13  Contrary to [12], touch [-] side of the tester to DIP-
IPM DCL2 terminal, and [+] side to [N] of DIP-IPM
(soldered part) to measure the resistance. Normal if
all three terminals have 10 kΩ or greater. (Resistance
gradually increases during measurement.)
Contact with specied terminals
to measure.
Tester
Checking Method of Resistance for Inrush Current Prevention (Built-in Thermal Fuse)
(Measure the resistance under 1 kΩ range of a circuit tester.)
N O T E
DO NOT use a digital tester.
By placing the
+
side of tester to the
+
side of DM1
(soldering portion) on inverter PCB and the
-
side of
tester to DCL1 on inverter PCB, measure the resistance.
If the resistance is around 500Ω, it is normal. If the resist-
ance is 0Ω or innity Ω, it is abnormal.
DM1 -
DCL1
+
-
Contact with specied terminals
to measure.
Tester