8 Troubleshooting
293
SMGB0087 rev.0 - 12/2013
8
RAS-(2-2.5)HVNP1 / RAS-3HVNP1
Item
Item Indication data
Check
number
Indic. Indic. Contents
Input/output state of outdoor micro-
computer
01
SC
Indicates only for the segments corresponding to the equipment in
the gure. (See gure above)
Capacity of operating indoor unit 02
oP 11
00~96
In case that capacity is higher than 100, the last two digits ash
Inverter order frequency to compressor 03
HI 74
0~115 ( Hz)
In case that frequency is higher than 100Hz, the last two digits
icker
Indoor order frequency to compressor 04
H2 74
0~115 ( Hz)
In case that frequency is higher than 100Hz, last two digits icker
Air ow ratio 05
o 80
00~100 (%)
In case that air ow ratio is 100%, “00” ashes
Outdoor unit expansion valve opening 06
Eo 30
00~100 (%)
In case that expansion valve opening is 100%, “00” ashes
Temperature at the top of compressor 07
d 02
00~142 (ºC)
In case that temperature is higher than 100ºC, the last two digits
ash
Evaporating temperature at heating 08
E 2
-19~80ºC
Ambient air temperature 09
o -3
-19~80ºC
Control PCB information 10
20
Internal information of the PCB
Control PCB information 11
A1 12
Internal information of the PCB
Inverter secondary current 12
A2 20
00~199 (A)
In case that current is higher than 100ºC, the last two digits ash
Outdoor unit address 13
nA 00
00~63
In case of twin/triple/quad-type unit,
the information of 2nd to the 4th
indoor units is indicated repeatedly.
The right character of the indication
represents the indoor unit setting
number.
Single: A
Twin: A, b
Triple: A, b, c
Quad: A, b, c, d
Indoor unit expansion valve opening 14
EA 20
00~100 (%)
In case that opening is
100%. “00” ashes
Liquid pipe temperature of indoor unit
(freeze protection)
15
LA 05
-19~127 (ºC)
Indoor unit intake air temperature 16
iA 28
-19~127 (ºC)
Indoor unit discharge air temperature 17
oA 20
-19~127 (ºC)
Cause of indoor unit stoppage 18
dA 05
(See table at the next page)
Total accumulated operation time of
Compressor
19
U 00
0 to 199 (x 10 hours)
Alternately upper 2 digits and lower 2 digits are indicated every
0.5 sec.
Accumulated operation time of com-
pressor (can be reset to zero for in-
stance when compressor is replaced)
20
cU 00
0 to 199 (x 10 hours)
Alternately upper 2 digits and lower 2 digits are indicated every
0.5 sec. (Push PSW1 and PSW3 during 5 seconds for resest)
Alarm code for abnormal stoppage of
compressor
21
AC 08
Alarm code on compressor
Cause of stoppage at inverter 22
i 1
(See table at the next page)
Abnormal data record 23
n1 00
One of the abnormal data record from latest (n1) to oldest (n9) is
indicated. Alarm code or cause code is indicated.
Total capacity of indoor unit connected 24
CP 22
00~96
In case that capacity is higher than 100, the last two digits ash
Quantity of connected indoor units 25
AA 2
00~64
Refrigerant adress 26
GA 0
00~63