EasyManua.ls Logo

Hitachi RAS-(4-12)HNP(1)(E) - Page 370

Hitachi RAS-(4-12)HNP(1)(E)
498 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Servicing
356
SMGB0087 rev.0 - 12/2013
5  Open the soundproof cover wrapped around the compressor and
remove the terminal box cover of the compressor body. Disconnect
the compressor wires in the terminal box and remove the thermis-
tor on top of the compressor.
Check the wiring color and layout when disconnecting. Connecting
wires in wrong order at reassembling may result in compressor da-
mage.
1
2
3
4
5
6
1
Compressor-Top Thermistor Mount
onto Terminal Cover with Metal
Fitting.
2
Yellow.
3
White.
4
Red.
5
Terminal cover.
6
M5 nut.
6  Remove the suction and discharge pipes from the compressor.
Be sure to separate the blazing burner ame sufciently from the
wires and electrical components around the brazed part in order
to avoid burning.
1 Blazing Discharge pipe.
2
Blazing Suction pipe.
7  Remove push nuts A and B which xes the compressor.
Lift the compressor and remove from the unit body. (C in
the gure does not have a push nut).
a.  Check if the Faston terminal has any abnormali-
ty when replacing the compressor. (Ensure the pull
out force greater than 20 N). If the Faston terminal is
identied faulty replace to a new one.
b.  Ensure the xture of the lead wires.
1 Compressor
2
Accumulator
3
Push nut
4
Vibration-proof rubber.
5
Two push nuts.
6
Three vibration-proof rubber.
7
Accumulator.