EasyManua.ls Logo

Honeywell GENT Nano panel-based - Lithium Battery

Honeywell GENT Nano panel-based
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lithium battery
&
There are LETHAL VOLTAGES present on the Power supply assembly.
Therefore it is important when working on the MCB or PSU board to completely
power down the panel. The mains supply must be switched off and the battery
supply disconnected.
The 3V lithium battery suppled in the spares pack must be fitted to the Main control board (MCB).
The battery provides the power to retain the system configuration data in the event of panel power
failure or disconnection. See the 'Links' section for procedures on how to gain access to the Main
control board (MCB).
&
Always use the recommended replacement battery. As there is a risk of
an explosion if incorrect battery is used.
4188-949 issue 3_05/10_Nano Comms inst. 15
Nano panel based system
Lithium battery
A VIEW OF THE ELECTRONIC MODULE
WARNING
Removal of
cover exposes
live parts
DANGER
Place lithium battery with marking on top into the
socket BATT3. The socket BATT3 is located on the
Main Control Board.
Push the battery down until it locks into the socket.
To remove the lithium battery hold it by the sides
‘B’ and
g
entl
y
pull it out.
+
‘A
Power Supply
Assembly
Main Control Board
‘B’
‘B’
‘A
BATT3
LCD assembly

Table of Contents

Related product manuals