How to set up 'Maintenance visit reminder'
The maintenance visit reminder will appear on the display to remind responsible person(s) to arrange for the system to be maintained by the servicing organisation. The message is displayed at the
beginning of the reminder day and is automatically removed after 7 days. You will need to be at access level 4 to set up the reminder.
How to return 'System Configuration' to factory default settings
It is possible to reset the system configuration to factory default settings. You will need to be at access level 4 to use this function.
Commissioning instructions
64 4188-949 issue 3_05/10_Nano Comms inst.
How to set up 'Maintenance visit reminder'
Select
System >
Select
Select
Engineering
Default >
Select
Select
Config
SelectSelect
Note: Only the labels are retained.
16:15 Tue 16/02/10
WARNING! - This will reset the
configuration to factory defaults!!
ARE YOU SURE YOU WISH TO PROCEED?
Yes No
Menu
Yes
After configuration has been reset you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
After the configurations are reset you will need to power
down and power up the panel.
Select
Maintenance >
Select
Select
Engineering
Menu
Reminders
Select
Select
Set Maintenance visit reminder to ‘ON’
or ‘OFF’(factory setting)
Select the maintenance visit interval:
MONTHLY
QUARTERLY
HALF YEARLY
or YEARLY
10:15 Tue 16/02/10
Maintenance visit reminder is : [OFF]
Interval: [QUARTERLY]
Next visit - Day: [ 7] Month: [ 1]
Reminder message set to:
Line 1: [MAINTENANCE VISIT DUE ]
Line 2: [PLEASE CALL FOR SERVICE ]
Save Quit
Save
Set Day and Month of maintenance visit
Enter the Maintenance visit reminder message
To scroll range
To move to
next setting
Use these keys to
scroll the alphanumeric
character set.
To move to
next character
position
!”#$%&’()*+,-./012--89
:;<=>?@ABC--wxyz[\]^
_`abc---wxyz{|}~SPACE
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.