Typical device forms continued
4188-949 issue 3_05/10_Nano Comms inst. 39
Nano panel based system
How to view or change 'Device configuration'
16:35 Tue 16/02/10
Device:[ 25] Settings Find [OFF]
Label:[Device Label ]
Type: Beam Transmitter
Save Quit
Beam Transmitter
16:34 Tue 16/02/10
Device:[ 24] Settings Find:[OFF]
Label:[Device Label ]
Type: Beam Receiver
Assigned to Zone:[ 1]
Sensitivity States Night:[ 0] Day:[ 0]
Gain:[63]
Save Quit
Beam Receiver
16:38 Tue 16/02/10
Device:[ 29] Settings Find:[OFF]
Label:[Device Label ]
Type: Mains Powered LV Interface
Save Quit
S4-34440 Mains Powered Interface ¯
16:39 Tue 16/02/10
Device:[ 30] Settings Find:[OFF]
Label:[Device Label 34440 IF ]
Type: Mains Powered Interface
Save Quit
34440 Mains Powered Interface ¯
16:33 Tue 09/03/10
Device:[ 22] Settings Find [OFF]
Label: [Device Label ]
Type: O H + CO Sensor + Strobe/Speech
Assigned to Zone [ 1] Sect [ 2] ML: [OFF]
Sensitivity States : Night:[ 0] Day:[ 0]
Output Level:[-21dB ] Mode:[TONE]
Save Quit
2
Dual Optical Heat Sensor + CO Strobe / Speech
16:32 Tue 09/03/10
Device:[ 21] Settings Find [OFF]
Label:[Device Label ]
Type: O H + CO Sensor
Assigned to Zone:[ 1] ML: [OFF]
Sensitivity States Night:[ 0] Day:[ 0]
Save Quit
2
16:36 Tue 09/03/10
Device:[ 26] Settings Find [OFF]
Label:[Device Label ]
Type: Optical Heat Sensor + Sounder
Assigned to Zone:[ 1] Sect:[ 2] ML: [OFF]
Sensitivity States Night:[ 0] Day:[ 0]
Output Level: [-0dB ]
Save Quit
Dual Optical Heat Sensor + CO
Optical Heat Sensor + Sounder
16:37 Tue 09/03/10
Device:[ 27] Settings Find [OFF]
Label:[Device Label ]
Type: Heat Sensor + Sounder
Assigned to Zone:[ 1] Sect:[ 2] ML: [OFF]
Sensitivity States Night:[ 0] Day:[ 0]
Output Level: [-0dB ]
Save Quit
Heat Sensor + Sounder
16:40 Tue 16/02/10
Device:[ 31] Settings Find:[OFF]
Label:[Device Label ]
Type: Voice Sounder
Assigned to Sect:[ 2]
Output Level: [-0dB] Mode:[TONE]
Save Quit
Voice Sounder
16:42 Tue 16/02/10
Device: [ 12] Settings Find:[OFF]
Label:[Device label ]
Type: Manual Call Point
Assigned to Zone:[ 1]
Save Quit
Manual Call Point
16:43 Tue 16/02/10
Device:[ 15] Settings Find:[OFF]
Label:[Device Label ]
Type: Single Output MV Interface
Assigned to Sect:[ 2]
Save Quit
Single Output MV Interface
16:44 Tue 16/02/10
Device:[ 20] Settings Find:[OFF]
Label:[Device Label ]
Type: Heat Sensor
Assigned to Zone:[ 1] ML: [OFF]
Sensitivity States Night:[ 0] Day:[ 0]
Save Quit
Heat sensor
TONE
‘VOICE’
TONE
VOICE’
¯ The Zone and sector settings are possible via
Setting -> Loop-> Channel.
¯ The Zone and sector settings are possible via
Setting -> Loop-> Channel.
16:43 Tue 16/02/10
Device:[ 55] Settings Find:[OFF]
Label:[Device Label ]
Type: Single Output LV Interface
Assigned to Sect:[ 2]
Save Quit
Single Output LV Interface