How to view 'Diagnostics' data
The diagnostic data of mains, battery, loop, 24V supply, master alarm circuits, class change, external evacuate, earth and repeat indicator can be displayed for engineering use. This information is for
engineering use only and the illustration below show typical values. You will need to be at Access level 4 to view diagnostics data.
How to view 'Site data' version
The Site Data version number is a count of each upload of the configuration made from the Nano commissioning tool. You will need to be at access level 2 or above to view site data version.
4188-949 issue 3_05/10_Nano Comms inst. 29
Nano panel based system
How to view 'Diagnostics' data
10:15 Tue 16/02/10
Site Data Version Details
Version Number: 001
Last Updated: 16-02-2010
Back
Select
System >
Select
Engineering
Menu
Versions
Select
Site Data
Select
Bac
k
Select
System >
Select
Engineering
Diagnostics
Select
16:15 Fri 26/04/08
PSU Voltages
Mns BtN BtL ChN ChR LpV 24V
207 207 206 255 031 196 047
MCB Voltages
MA1 MA2 Cls Evc Ear 24V Rpt
086 084 127 128 090 205 209
Update Back
Mains supply
Battery supply
Battery load test
Charger Nominal
Charger Recharge
Loop voltage
24V supply
Master alarm circuit 1
Master alarm circuit 2
Class Change
External Evacuate
Earth
24V supply
Repeat indicator
Update
Select ‘Update’ to refresh the voltage values.