How to enable/disable Master alarms, Fire relay and Evac. input
You can manually enable or disable the master alarms, fire relay and evacuate input. You can also view the current state of master alarms, fire relay and evacuate input. You will need to be at access
level 2 or above to enable or disable these functions.
How to enable or disable and set a Sector activation control
You can manually enable or disable alarm activation control and view current state of the sector. You will need to be at access level 2 or above to enable or disable sectors. You will need to be at
access level 3 or above to change the sector activation control..
4188-949 issue 3_05/10_Nano Comms inst. 63
Nano panel based system
How to enable/disable Master alarms, Fire relay and Evac. input
Select a ‘Sector’ from a range 1 to 16
10:15 Tue 16/02/10
Sector: [ 1]
Label : Sector Label
Activation Control : SILENCE
Status Control : [ENABLED ]
Current State : IDLE
Save Quit
Save
Menu
Sectors
SelectSelect
Alarms >
Select
User
Select ‘Sector’ status:
Sector ‘ENABLED’ (factory default setting) or Sector ‘DISABLED’
To scroll range
To move to
the next setting
Disablement
[amber LED]
Sounder
Disablement
[amber LED]
Select Activation
At view you can only view the set Activation Control
At and above you can change the Activation Control to:
- SILENCE
- TEST
- CLASS
- ALERT
or - EVACUATE
AL2
AL3
Menu
User
10:15 Tue 16/02/10
Alarm Status
State Enable Status
Master Alarms : INACTIVE [ ENABLED ]
Fire Relay : INACTIVE [ ENABLED ]
Evacuate Input: INACTIVE [ ENABLED ]
Save Quit
Set Alarm status of:
‘Master Alarms’ Enable Status to ENABLED (Factory default setting) or DISABLED
‘Fire Relay’ Enable Status to ENABLED (Factory default setting) or DISABLED
‘Evacuate Input’ (INACTIVE) to ENABLED (Factory default setting) or DISABLED
Save
Here the ‘Sounder Disablement’
LED is only lit when the
Master Alarms are disabled.
Select
Alarms >
Select
Other
Select
To scroll range
To move to
the next setting
Disablement
[amber LED]
Sounder
Disablement
[amber LED]