Time averages explained
The time averages provide sensor performance data with the display showing the latest time average value, foreground (fast) time average values T1 to T5 and background (slow) time average values
T6 to T11. These values are used by the panel to make fire detection decision.
Foreground (fast) time average
readings
Background (slow) time average readings
T
Latest
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11
On
demand
80mS 320mS 1.28S 5.12S 20.48S 1.36min 5.46min 21.84min 1.45hr 5.82hr 23.3hr
Normally reads 252, unless there is
activity on this channel.
Device type S-Quad Analogue Channels Typical
Time average
T
latest
(new)
Heat Sensor 2 - heat 66
Heat Sensor Sounder 2 - heat 66
Dual Optical Heat Sensor 1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor Strobe 1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor Sounder 1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor Speech Strobe 1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor CO 1 - optical (forward)
2 - heat
3-CO
4 - optical (backward)
25
66
25
40
Dual Optical Heat Sensor CO Speech Strobe 1 - optical (forward)
2 - heat
3-CO
4 - optical (backward)
25
66
25
40