How to conduct a 'Display Test'
It is possible to check if all the LEDS and the display of the panel have not failed by conducting a display test. You will need to be at Access Level 2 or above to conduct a Display test.
How to view the panel 'Firmware'
To check you have the latest panel firmware to support the installed system you can view the firmware of the Main Controller, Loop driver and PSU.
You will need to be at Access Level 2 or above to check the panel firmware.
How to view the 'Historic' events log
The Historic events log holds up to 999 records of events in the system. You can scroll through all the events with event number 1 being the latest event. You can also print a range of events to a printer,
providing a printer is connected to the panel.
Commissioning instructions
22 4188-949 issue 3_05/10_Nano Comms inst.
How to conduct a 'Display Test'
10:15 Mon 15/02/10
Firmware Version Numbers
Main Controller V2.XX xx-xx-10
Loop Driver V1.03 15-02-09
Vig Compact PSU V2.05 01-07-08
Back
Select
System >
SelectSelect
Engineering >
Menu
Versions
SelectSelect
Firmware
SelectSelect
Bac
View
Print
Select
Select
Historic >
Select
Menu
Select
6:15 Mon 15/02/10
Event Log (200)
1: 10:37:20 Sun 14/02/10
Zone Disabled
Zn 001:Zone 1
Quit
10:15 Mon 15/02/10
Print Event Log (200)
First Event To Print [001]
Last Event To Print [005]
Print Quit
To view other historic events
Logs
Print
Quit
The ‘Print’ option is only valid at
Access Level 2 or higher and
only when a printer is connected
to the panel.
To scroll the
range
To move to
the next setting
POWER
FIRE
[green LED]
FAULT
[amber LED] [red LED]
[amber LEDs]
[red LEDs]
Test duration is
approximately
8 seconds.
Menu
Select
System >
Select
User
Display Test
Select
Audible
Buzzer