How to set-up the 'Class Change input'
The class change input application is used in schools to output a class change alarm via the sounders in selected sectors to signify end of class.
You will need to be at access level 3 or above to configure class change input.
You will also need to assign class change to activate sectors see section headed 'How to set-up 'Sector' mode, label and activation'.
Commissioning instructions
56 4188-949 issue 3_05/10_Nano Comms inst.
How to set-up the 'Class Change input'
10:15 Tue 16/02/10
External Input Settings
External Evacuate Input Used : [NO ]
External Evacuate Input Latches : [NO ]
Class Change Input Used : [NO ]
Save Quit
External Inputs
Select
Set the ‘Class Change’ input
use requirement to - ‘NO’ (factory default setting) or ‘YES
Save
More >
Select
Select
System >
Select
Settings
Menu
To scroll the
settings
To move to the
class change
field
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
Class Change
2 - 10K Ohms -
resistors must be
fitted as shown.
+VE
0V
DRN
CLASS CHANGE
PP8
Switch
Normally open contacts
CLASS CHANGE ALARM
To stop the class change alarms
simply release the switch.
by Honeywell
POWERFAULT
FIRE
Test
Delay
Verify
SounderFault
Zone2
Zone6
Zone10
Zone14
Zone3
Zone7
Zone11
Zone15
Zone4
Zone8
Zone12
Zone16
Disablement
Zone1
Zone5
Zone9
Zone13
SystemFault
Sound
Alarms
Silence
Alarms
PowerFault
Reset
Cancel
Buzzer
Sounder
Disablement
042bc
EN54 Parts 2 & 4
12:30 Tue 16/02/10
[MENU]
Nano Fire Alarm System
Gent by Honeywell