How to set-up 4-channel interface devices on the loop
You can configure any 4-channel interface devices on the loop. You will need to be at Access level 3 or above to setup a 4-channel interface device on the loop. This form allows you to set-up the
channel label, mode and assignment to zone and sector.
Note the channel 'Mode' settings are only applicable for the 4-channel LV interface units. The mains powered 4-channel interface unit can only be configured using the hardware switches.
How to enable/disable a channel of a 4-channel interface device
You can enable or disable a channel of a 4-channel interface unit. You will need to be at access level 3 (factory default) unless it is configured for operation at access level 2 during commissioning.
4188-949 issue 3_05/10_Nano Comms inst. 49
Nano panel based system
How to set-up 4-channel interface devices on the loop
Menu
Select
Loop >
Select
Settings
Channels
Select
10:15 Tue 11 /07/08
[Device 7 Channel 1 ]
Label : [Channel 1 ]
Mode: [N/C SUPERVISORY ]
Supervisory Functions: [SILENCE ALARMS ]
Channel Zone:[ 1]
Channel Sector:[ 1]
Save Quit
#
SYSTEM RESET
DISABLE ZONE
DISABLE SECTOR
DAY / NIGHT SWITCH
VERIFY ALARMS
ACTION SECTOR
ZONE IN TEST
CLASS CHANGE
EXTERNAL EVAC
SILENCE ALARMS
Select a Device channel from a range 1 to 4
Save
UNCONNECTED
N/O RELAY OUTPUT
or (N/OFF SECTOR OUTPUT~)
N/C RELAY OUTPUT
or (N/ON SECTOR OUTPUT~)
NORM OFF LED OUTPUT
NORM ON LED OUTPUT
N/C FIRE
N/O FIRE
N/C FAULT
N/O FAULT
N/C SUPERVISORY #
N/O SUPERVISORY #
DELAYED N/C FIRE
DELAYED N/O FIRE
DELAYED N/C FAULT
DELAYED N/O FAULT
DELAYED N/C SUPERVISORY #
DELAYED N/O SUPERVISORY #
CONVENTIONAL ZONE
Channel assigned to zone from a range 1 -16
Channel assigned to sector from a range 1 -16
Edit the label for the interface
Use these keys to
scroll the alphanumeric
character set.
To move to
next character
position
!”#$%&’()*+,-./012--89
:;<=>?@ABC--wxyz[\]^
_`abc---wxyz{|}~SPACE
To scroll the
range
To move to
next setting
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
~ Applicable for new mains powered interface only.
10:15 Tue 16/02/10
[Device 7 Channel 1 ]
Label: Channel 1
Status: [Enabled ]
Save Quit
Select
Loop >
SelectSelect
User
Menu
Channels
SelectSelect
Select
Select a Device channel from a range 1 to 4
To scroll range
To move to
the next setting
Enable or Disable the Device channel