How to view or change 'Device configuration'
&
The Nano panel recognises the 34420 Interface Unit as having 1-Output channel only. The ‘confirmation Input’ channel of this interface unit is not recognised nor used when
this unit is connected to the Nano loop circuit.
Two methods are shown for making changes to device configuration.
4188-949 issue 3_05/10_Nano Comms inst. 37
Nano panel based system
How to view or change 'Device configuration'
#
SILENCE ALARMS
SYSTEM RESET
DISABLE ZONE
DISABLE SECTOR
DAY/NIGHT SWITCH
VERIFY ALARMS
ACTION SECTOR
ZONE IN TEST
CLASS CHANGE
EXTERNAL EVAC
To scroll the
range
To move to
next setting
Devices
10:15 Tue 16/02/10
Device : [ 1] Settings Find [OFF]
Label:[Device Label ]
Type: O H Sensor + Strobe/Speech
Assigned to Zone:[ 1] Sect: [ 1] ML: [OFF]
Sensitivity States Night: [ 0] Day:[ 0]
Output Level:[-0dB ] Mode:[TONE]
Save Quit
2
Select an Output level for the device from a range:
-0dB, -3dB, -6dB, -9dB, -12dB or -15dB, -18dB, -21dB
Set ‘Device’ assignment to ‘Zone’ and ‘Sector’
from a range 1-16.
Select ‘Sensor State’ for ‘Day’ and ‘Night’ modes
from a range - 0 (factory default setting) to 15
Select a ‘Device’ from a range 1 to 127
‘Find Device’ ON / OFF option
Save
This example shows the display of a
Dual Optical Sensor Sounder and Strobe
Edit the ‘Device’ label
Select ‘TONE’ or
‘VOICE’ mode
UNCONNECTED
N/C FIRE
N/O FIRE
N/C FAULT
N/O FAULT
N/C SUPERVISORY #
RELAY OUTPUT*
LED OUTPUT*
N/O SUPERVISORY #
DELAYED N/C FIRE
DELAYED N/O FIRE
DELAYED N/C FAULT
DELAYED N/O FAULT
DELAYED N/C SUPERVISORY #
DELAYED N/O SUPERVISORY #
CONVENTIONAL ZONE
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
Select
10:15 Tue 16/02/10
Loop Map
1+ Device 1
2 Device 2
3 Device 3
4 Device 4
Select Quit
9
9
9
9
Menu
Select
Loop >
SelectSelect
Engineering Map
Select
Settings
View
Select
Select
Loop >
Settings
Menu
Select
Method 1 at access level 3 or above
Method 2 at access level 4
* Only applicable for 4 channel interface
Monitored Line
‘ON’ or ‘OFF’
(factory default
setting).