EasyManua.ls Logo

Honeywell GENT Nano panel-based - How to Enable or Disable a Zone; How to Place a Zone in Test Mode

Honeywell GENT Nano panel-based
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
How to 'Enable' or 'Disable' a Zone
You can manually disable a zone to prevent system going into a fire condition in the event of a fire being detected in the zone. ~You can reenable the disabled zone at anytime. You will need to be at
Access level 2 or above
How to place a Zone in 'Test Mode'
The Zone 'Test mode' function is used when testing devices in a zone. It allows the engineer to test zones without having to return to the panel to silence alarms and reset.
While the panel is in the Zone Test mode and following a fire event the alarm sounds for 5 seconds and then automatically performs the silence alarm sequence and thereafter a panel reset. The panel
inhibits the operation of delays and fire relay. For information on how to conduct a fire test see page 60.
¨
All zones of the system that are not in test mode will operate normally.
"
On completion of all commissioning work, switch Off the Zone Test mode and notice the Test indicator also switches Off.
4188-949 issue 3_05/10_Nano Comms inst. 61
Nano panel based system
How to 'Enable' or 'Disable' a Zone
10:15 Tue 16/02/10
Zone : [01]
Label: Zone Label
Status : [ ENABLED ]
Test : [ NO ]
Save Quit
Select a ‘Zone’ from a range 1 to 16
Select the ‘Zone’ status:
Zone ‘ENABLED’ (factory default setting)
or Zone ‘DISABLED’
Save
Menu
Select
Zones
Select
User
To scroll the
range
To move to
the next setting
Disablement
[amber LED]
10:15 Tue 16/02/10
Zone : [01]
Label: Zone Label
Status : [ ENABLED ]
Test:[NO]
Save Quit
Place the ‘Zone’ in to ‘Test mode’ - NO (factory default setting) or YES
Select a ‘Zone’ from a range 1 to 16
Save
Menu
Select
Zones
SelectSelect
User
To scroll the
range
To move to
the next setting
Test
[amber LED]
Only the ALARM sectors are
actioned in Test, the PLANT
sectors are not affected.

Table of Contents