How to set 'Zone' label, mode and link to another zone
You will need to be at access level 3 or above to set zone label, mode and link.
How to view 'Devices' assigned to a 'Zone' and change device configuration
You will need to be at access level 3 or above to view all the devices assigned to a zone and selectively look and change each device configuration.
Commissioning instructions
44 4188-949 issue 3_05/10_Nano Comms inst.
How to set 'Zone' label, mode and link to another zone
Select
Settings
Menu
10:15 Tue 16/02/10
Zone:[ 1] Basic Settings
Label:[Zone Label ]
Mode: [ NORMAL ]
Linked to Zone :[0]
Save Quit
Zones >
Select
Configuration
Select
Enter the ‘Zone’ label
Select detection mode of the ‘Zone’:
‘NORMAL’ (factory default setting) or
‘2 - DETECTORS’ or
‘2 - ZONES’
Select a ‘Zone’ from a range 1 to 16
Select linkage of the ‘Zone’ to another
zone from a range 1 to 16
Save
To scroll the
range
To move to
next setting
Use these keys to
scroll the alphanumeric
character set.
To move to
next character
position
!”#$%&’()*+,-./012--89
:;<=>?@ABC--WXYZ[\]^
_`abc---wxyz{|}~SPACE
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
10:30 Tue 16/02/10
Zone[ 1] Assigned Device list :
Device 1 Label
Device 2 Label
Device 3 Label
Device 4 Label
Select Back
For the Selected device it is possible to
view and change the device configuration.
Select a ‘Zone’ from a range 1 to 16
Select
Select a ‘Device’ in the ‘Zone’
10:31 Tue 09/03/10
Device: [ 2] Settings Find [OFF]
Label: [Device Label ]
Type : O H Sensor Sounder Strobe
Assigned to Zone: [ 1] Sect: [ 1] ML: [OFF]
Sensitivity States Night: [ 0] Day:[ 0]
Output Level: [-0dB ]
Save Quit
2
A typical ‘Device’ view.
For information on editing ‘Device details’ see section
headed ‘Device details’.
DEVICE
Select
Zones >
Select
List of Devices
Select
Settings
Menu
Save
To scroll the range