How to set up an 'External Evacuate input'
The External evacuate input operates in the same way as the Sound/Silence buttons. The input can be set as a latched or non latched input.
You will need to be at access level 3 or above to set up the external evacuate input.
4188-949 issue 3_05/10_Nano Comms inst. 55
Nano panel based system
How to set up an 'External Evacuate input'
10:15 Tue 16/02/10
External Input Settings
External Evacuate Input Used : [NO ]
External Evacuate Input Latehes : [NO]
Class Change Input Used : [NO ]
Save Quit
External Inputs
Select
Set the ‘External Evacuate’ input
use requirement - ‘NO’ (factory default setting) or ‘YES
Save
More >
Select
Select
System >
Select
Settings
Menu
To scroll the
settings
To move to
External evacuate
input field
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
by Honeywell
POWERFAULT
FIRE
Test
Delay
Verify
SounderFault
Zone2
Zone6
Zone10
Zone14
Zone3
Zone7
Zone11
Zone15
Zone4
Zone8
Zone12
Zone16
Disablement
Zone1
Zone5
Zone9
Zone13
SystemFault
Sound
Alarms
Silence
Alarms
PowerFault
Reset
Cancel
Buzzer
Sounder
Disablement
042bc
EN54Parts 2 & 4
12:30 Tue16/02/10
[MENU]
Nano FireAlarm System
Gent by Honeywell
Evacuation Input
2 - 10K Ohms -
resistors must be
fitted as shown.
Switch
Normally open contacts
+VE
0V
DRN
EXT.EVAC.
PP8
Normal
Active
O
I
O
I
Audible
Buzzer
FIRE
Common fire LED
(Flashing indication)
red LED
The enabled ALARM sectors are activated. No
PLANT sectors will be activated.
If set up as non latching then when the input
returns to normal the system will automatically
silence.
If set up as latching then when the input returns
to normal the system will silence on Silence
Alarms.
Manually silencing the system while the external
evacuate input is active will cause a fault to be
raised until the input is cleared.