How to change access levels of 'Buzzer' & 'Device Disablement'
By default the buzzer can be cancelled at access level 2 and devices plus interface channels can be disabled at access level 3. It is possible to change the access levels of these controls, however you
will need to be at access levels 3 or above to make these changes.
How to change the 'Alarm Controls' settings
After alarms have been silenced during or following a fire condtion the same alarms can be activated again by pressing the'Sound Alarms' button, providing the 'Resound' mode is configured. In the
same scenario if configured for 'Sound' mode and on pressing the 'Sound alarms' button it will activate all the sector alarms. The Fire relay can be configured to be active with the 'Sound alarms' button.
You will need to be at access level 3 or above to change 'Sound alarms' button settings.
Commissioning instructions
58 4188-949 issue 3_05/10_Nano Comms inst.
How to change access levels of 'Buzzer' & 'Device Disablement'
10:15 Tue 16/02/10
Access Level Settings
Cancel Buzzer Level : [2]
Disablement Level : [3]
Save Quit
Access Levels
Select
The ‘Cancel buzzer’ function can be either at Access level 1 [1] or at Access Level 2 [2](factory default setting)
Save
The ability to disable devices can be at level 3 [3] (Factory default setting) or at Access level 2 [2]
More >
Select
Select
System >
Select
Settings
Menu
To scroll the
range
To move to the
next setting
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
10:15 Tue 16/02/10
Sound Alarms Settings
Sound Alarms Mode : [RESOUND]
New Fire Resounds Alarms : [NO ]
Sound Alarms Operates Fire Relay [NO]
Save Quit
Save
Set ‘Sound alarm’ to operate Fire relay:
‘NO’ Factory default setting) or ‘YES’
Set Sound Alarm mode to ‘SOUND’ or
‘RESOUND’ (Factory default setting).
Menu
Select
Alarms >
Select
Settings
Controls
Select
To scroll the
range
To move to
next setting
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
New Fire to resound alarms of previous
fire events as well ‘Yes’ or ‘NO’
Factory default setting)