How to 'Back-up' site data to Flash memory
Once the panel has allocated addresses to all the loop devices and the loop has started you will need to back-up the site data to the Flash memory at the panel. Any subsequent changes to the
configuration and labels during commissioning will also need to be backed-up. When the commissioning tool is used to transmit the custom configuration to the panel, the new data at the panel must be
backed-up to the panel memory. You will need to be at access level 3 or above to back-up site data to flash memory.
How to 'Restore' configuration data from Flash memory
If for some reason the changes made to the configuration since previous back-up is not known then you can restore the previous back-up. You will need to be at access level 3 to restore configuration
data.
Commissioning instructions
28 4188-949 issue 3_05/10_Nano Comms inst.
How to 'Back-up' site data to Flash memory
10:15 Tue 11/07/08
This will overwrite the configuration
data in FLASH !
Are you sure?
Yes No
System >
Engineering >
Menu
Site Data > Backup
Yes
10:15 Tue 16/02/10
This will overwrite the configuration
data in FLASH !
Are you sure?
Yes No
System >
Engineering
Site Data > Backup
Yes
Select Select Select Select
Ensure the write protect link P9 on the MCB in configured in the
ENABLED position to allow back-up of data to memory.
10:15 Tue 11/07/08
This will overwrite the configuration
data in RAM with the data from FLASH !
Are you sure?
Yes No
System > Site Data >
Restore
Yes
10:15 Tue 16/02/10
This will overwrite the configuration
data in RAM with the data from FLASH !
Are you sure?
Yes No
System > Site Data >
Restore
Select Select Select Select
Menu
Engineering