Visual and audible indication of 'Find Device'
Sensors and MCP
¨
A S-Quad fire sensor or manual call point will operate its LED for 0.5 second On and 0.5 second Off repeated.
Sounders and S Cubed
¨
Each S cubed or S-Quad with sounder device will provide an audible tone and/or visual indication for 0.5 second On and 0.5 second Off repeated. If the device operates in voice
mode then the pre-tone followed by a full test message will be played.
Interface units
&
Ensure Interface outputs are not connected to external equipment at this stage of commissioning. These must be tested in accordance with project
recommendations.
¨
Each interface output will in turn be activated for 0.5 second On and 0.5 second Off, this will repeat.
How to 'Print' the Loop map
You can print the loop map to a local printer connected to the panel. You will need to be at access level 4.
"
A printout will only print the first 15 characters of a label due to the limit of 40 characters per line on the handheld printer.
4188-949 issue 3_05/10_Nano Comms inst. 27
Nano panel based system
How to 'Print' the Loop map
10:15 Tue 16/02/10
Warning! Selecting this option will
cause the complete loop map to be
printed out on the serial printer.
ARE YOU SURE YOU WISH TO PROCEED?
Yes No
Menu
Select
Loop >
SelectSelect
Engineering Map
Select
Devices 2 and 3 are on a Spur
A after the device number
indicates the device is
SAFE addressed.
+
Print
Select
Addr Prev Next Spur Loc. Label
1 END1 4 2 LOOP Device 1
2 1 3 SPUR Device 2
3 2 O/C SPUR Device 3
4 1 5 O/C LOOP Device 4
5 4 6 LOOP Device 5
6 5 END2 LOOP Device 6
Typical printout