22 www.honeywell.com
NetAXS™ NX4L1 Installation Guide
Installation
4.2 Typing the Field Wiring in the NX4L1 Cabinet
Figure 2: Tying the Field Wiring in the NX4L1 Cabinet
Pb
Pb
and symbols represent wire
tie points.
Wiring shown as ||||||||||||||||||||||||||||
represent shrink wrap barrier
protection (0.028 inch thickness
minimum) where spacing between
non-power-limited and power-limited
wiring is less than 0.25 inches.
Location of wire tie points
and suggested routing of
Class 2 power-limited field
wiring to maintain a
minimum of 0.25 inch
spacing from
non-power-limited wiring