EasyManuals Logo

Honeywell NETAXS NX4L1 User Manual

Honeywell NETAXS NX4L1
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
NetAXS™ Standalone Operation
Standalone Commands
NetAXS™ NX4L1 Access Control Unit Installation Guide, Document 7-901099V3 69
3.0 Standalone Commands
CAUTION Use the following commands, in the order they are listed, to configure
the NetAXS™ panel.
1. T command: Sets the panel’s time
2. D command: Sets the panel’s date
3. L command: Creates time zones for use by the cards
4. C command: Adds or deletes cards from the panel
5. W command: Program each input for either NO/NC and supervised or
non-supervised operation
6. P command: Sets interlocks between input points and/or output points
Note: In all examples, the underscore character “_” indicates a space and <CR>
indicates a carriage return.
3.1 T (Time) Command
_T=pn_hh:mm<CR>
Variables:
pn = panel number (1–31)
hh = hours (0–23) (Military time)
mm = minutes (00–59)
Example 1
_T=1_08:30<CR>
This command would set panel 1 to a time of 8:30 AM.
Example 2
_T=6_18:15<CR>
This command would set panel 6 to a time of 6:15 PM.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NETAXS NX4L1 and is the answer not in the manual?

Honeywell NETAXS NX4L1 Specifications

General IconGeneral
BrandHoneywell
ModelNETAXS NX4L1
CategoryControl Unit
LanguageEnglish

Related product manuals