NetAXS™ Standalone Operation
Standalone Commands
NetAXS™ NX4L1 Access Control Unit Installation Guide, Document 7-901099V3 69
3.0 Standalone Commands
CAUTION Use the following commands, in the order they are listed, to configure
the NetAXS™ panel.
1. T command: Sets the panel’s time
2. D command: Sets the panel’s date
3. L command: Creates time zones for use by the cards
4. C command: Adds or deletes cards from the panel
5. W command: Program each input for either NO/NC and supervised or
non-supervised operation
6. P command: Sets interlocks between input points and/or output points
Note: In all examples, the underscore character “_” indicates a space and <CR>
indicates a carriage return.
3.1 T (Time) Command
_T=pn_hh:mm<CR>
Variables:
pn = panel number (1–31)
hh = hours (0–23) (Military time)
mm = minutes (00–59)
Example 1
_T=1_08:30<CR>
This command would set panel 1 to a time of 8:30 AM.
Example 2
_T=6_18:15<CR>
This command would set panel 6 to a time of 6:15 PM.