68 www.honeywell.com
NetAXS™ Standalone Operation
Standalone Settings
2.0 Standalone Settings
2.1 NetAXS Panel Hardware Settings
• Configure the system with an RS-232 connection according to Figure 22 on
page 46.
• Set DIP switches 1 through 5 to define the panel number (see Table 5 on page 38).
Panel number 0 is not valid.
• Set DIP switch 6 to the OFF position to place the panel into the Multidrop mode.
• Use a personal computer’s serial communications port (COM1 or COM2) and a
terminal emulation program to configure the NetAXS™ panel for normal
operation.
2.2 Communication Settings
• Baud Rate: 115200
• Data Bits: 8
• Parity: None
• Stop Bits: 1
• Flow Control: None
2.3 Emulation Settings
• Echo typed characters locally: YES
• Line Delay: 500 milliseconds
2.4 Verifying Communications
1. Press the spacebar.
2. Press the carriage return <CR>. “S?” appear for every online panel and indicates
proper communication between the terminal and panel.