Valves
94 customer.honeywell.com 70-6925
VP512 Unit Vent Pneumatic Control Valve
A normally open, single seated, straight-through or angle globe 
valve used for proportional control of steam or hot water in unit 
ventilator applications. Replacement devices are available for 
Johnson, Powers, Robertshaw, Barber-Colman, and older 
Honeywell devices.
• Equal percentage, high lift throttling guide provides accurate control 
over wide load variations. 
• Molded replaceable composition disc for tight shut-off. 
• Replaceable brass seat. 
• Self-adjusting, spring-loaded Teflon™ packing. 
• Back-seating allows repacking without shutting down or draining 
system. 
• Rotatable actuator for aligning air connection with control air piping. 
• Integral union connection to simplify installation and service.
Dimensions in inches (millimeters)
M18805A
NEAREST OBSTRUCTION
ALLOW 3-3/8 IN. (86 MM) APPROX 
FOR REMOVAL OF ACTUATOR
FROM VALVE
H- SWING RADIUS
(TO TOP OF STEM
BUTTON WITH
ACTUATOR REMOVED
AND VALVE CLOSED)
STEM 
BUTTON
G
SWING 
RADIUS
A
B
C
D
E
3/8
(10)
3-5/8
(92)
7/16
(11)
5-1/8
(130)
F
J
VALVE
SIZE
BODY 
TYPE
A BCDE FGH J
1
1 1/4
1 1/2
STRAIGHT
ANGLE
STRAIGHT
ANGLE
STRAIGHT
ANGLE
1-3/8 (35)
1-3/8 (35)
1-9/16 (40)
1-9/16 (40)
1-11/16 (43)
1-11/16 (43)
---
2-1/8 (54)
---
2-1/8 (54)
---
2-1/8 (54)
3 (76)
3 (76)
3-3/4 (95)
3-3/4 (95)
4-1/4 (108)
4-1/4 (108)
2-1/4 (57)
---
2-1/2 (64)
---
2-7/8 (73)
---
1-5/8 (41)
---
1-1/2 (38)
---
1-3/8 (35)
---
---
1-1/16 (27)
---
1-3/16 (30)
---
1-3/8 (35)
1-31/32 (50)
1-31/32 (50)
2-9/16 (65)
2-9/16 (65)
3-9/32 (83)
3-9/32 (83)
4-1/2 (114)
---
4-13/16 (122)
---
5-5/32 (131)
---
---
1-29/32 (48)
---
2-15/32 (63)
---
2-15/16 (75)