EasyManua.ls Logo

Honeywell Pneumatic Controls - Warm-Up;Heating Coil Control Sequence

Honeywell Pneumatic Controls
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pneumatic Control System Example
156 customer.honeywell.com 70-6925
Warm-Up/Heating Coil Control Sequence
Any time the Supply Fan (Fig. 78) runs and the return air
temperature is below 69F, Temperature Controller TC-1 trips
Snap-Acting Relay SA-1 to position Switching Relays SR-1 and
SR-2 to initialize warm-up control. Relay SA-1 also positions
Switching Relay SR-4 to disable cooling controls. Switching
Relay SR-2 opens all interior VAV box dampers and starts the
hot water pump. Relay SR-1 switches the hot water valve from
normal control to warm-up control via Controller TC-2 and
modulates the hot water valve to maintain a discharge air
temperature setpoint of 90F.
NOTE: Fan powered perimeter VAV boxes are cool in this
mode and operate with the fans on and at the mini-
mum airflow (warm air) setpoints. Reheat valves at
each box operate as needed. This allows the warm-up
cycle to operate the air handling unit (AHU) fans at a
reduced and low cost power range.
Fig. 78. Heating Coil Control.
M
M
Y
2
EP
2
EP
M
Z
X
P
CX
O
P
CX
O
M
P
CX
O
P
CX
O
SR-1
SR-3
SR-2
RA
70
BSM
TC-1
2
EP
DA
90
BSM
TC-2
SA-1
C-X < 69
C-O >71
SNAP
ACTING
RELAY
RETURN
AIR
RETURN FAN
OUTSIDE
AIR
TO COOLING
CONTROLS
TS-1
FROM
COOLING
CONTROLS
3-8 PSI N.O.
SIGNAL TO OPEN
ALL INTERIOR VAV
BOX DAMPERS AND
START HOT WATER PUMP
M10301
TO
COOLING
CONTROLS
SUPPLY FAN
AIR DURING COLD RETURN AIR (WARM-UP)

Table of Contents

Related product manuals