70-6925 39
Application Type: Pressure Reducing
Connection Size: Inlet and out air: 1/4 in. NPT (female) Air gage: 1/8
in. NPT (female)
Mounting: Bracket furnished
Accessories:
305917 2 in. diameter, 1/4 NPT center stem back mount Pressure
Indicating gauge (0 to 160 psi scale) with +/- 3% accuracy
305965 1-1/2 in. diameter, 1/8 NPT center stem back mount Pressure
Indicating gauge (0 to 30 psi scale) with +/- 4% accuracy
804191E 2-1/2 in. diameter, panel-mounted Pneumatic Pressure
Indicating Gauge (0 to 160 psi), 1/8 in. NPT connection, +/-3%
accuracy
Replacement Parts:
14003121-002 Filter for PP902A or B
14004203-001 Filter cartridge kit for PP902C and PP902D.
14004205-002 Filter Station Assembly for PP901, PP902A or B
316134B PP901A & B Diaphragm Repair Kit
316203A Pressure Regulator Valve Assembly, PP901A & PP901B,
PP902A,B.
Product Number
Inlet Pressure
Range Output Pressure Range
Includes Description(psi) (kPa) (psi) (kPa)
PP901A1004 45 to
150 psi
310 to
1034 kPa
primary pressure: adj.0
to 25 psi.
primary pressure: adj.0 to
172 kPa.
Gage tapping
to measure
the regulated
pressure.
High Pressure Diaphragm Operated
Reducing Valve with Built-in Adjustable
Relief Valve for Single Pressure Systems.
Includes Mounting Bracket and Gage Taps
But No Gages.
PP901B1002 45 to
150 psi
310 to
1034 kPa
primary pressure: adj.0
to 25 psi; secondary
pressure: adj. 0 to 5 psi
above primary rating
primary pressure: adj.0 to
172 kPa; secondary
pressure: adj. 0 to 34kPa
above primary setting.
Gage tapping
to measure
the regulated
pressure.
High Pressure Diaphragm Operated
Reducing Valve with Built-in Adjustable
Relief Valve for Dual Pressure Systems.
Includes Mounting Bracket and Gage Taps
But No Gages.
PP902C1009 45 to
150 psi
310 to
1034 kPa
primary pressure: adj.0
to 25 psi
primary pressure: adj.0 to
172 kPa.
Sub-micron
filter assembly
and two psig
gages.
Pressure Reducing Valve for Single
Pressure Systems, consists of a PP901A
Valve, a sub-micron filter station, 2 psig
gages, Interconnecting Pipe Fittings, and a
Mounting Bracket
PP902D1007 45 to
150 psi
310 to
1034 kPa
primary pressure: adj.0
to 25 psi; secondary
pressure: adj. 0 to 5 psi
above primary rating
primary pressure: adj.0 to
172 kPa; secondary
pressure: adj. 0 to 34kPa
above primary setting.
Sub-micron
filter assembly
and two psig
gages.
Pressure Reducing Valve for Dual Pressure
Systems, consists of a PP901B Valve, a
sub-micron filter station, 2 psig gages,
Interconnecting Pipe Fittings, and a
Mounting Bracket