EasyManua.ls Logo

Honeywell Pneumatic Controls - RP418, RP818 Electric;Pneumatic Relay; Electric-Pneumatic

Honeywell Pneumatic Controls
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Relays
52 customer.honeywell.com 70-6925
RP418, RP818 Electric/Pneumatic Relay
Electrically operated pneumatic switches used to interlock an
electrical system and a pneumatic control system. Replacement
devices are available for Johnson, Powers, Robertshaw, Barber-
Colman, and older Honeywell devices.
Usable as a diverting relay, a selector relay, or a stop and bleed
relay.
Mount and operate in any position.
Available with lead wires or junction box.
Line or low voltage models available.
RP418 & RP818 Typical Piping and Wiring Internal Connections
Type: Electric / Pneumatic Relay
Dimensions, Approximate: 2 7/8 in. high x 3 13/16 in. wide x 1 1/4 in.
deep (73 mm high x 97 mm wide x 32 mm deep)
Airflow Usage: 0.42 scfm (200 mL/s) at 20 psi (138 kPa) supply with 1
psi (7 kPa) pressure drop
Air Connections: Barbed fitting for 1/4 in. O.D. plastic tubing
Capacity: 0.075 Cv minimum
Operation: Energized: ports 1 and 3 connected, port 2 blocked
De-energized: ports 2 and 3 connected, port 1 blocked
Operating Humidity Range (% RH): 5 to 95% RH
Temperature Range: 0 F to 100 F (-18 C to +38 C)
Maximum Safe Operating Pressure: 50 psi (340 kPa)
Approvals:
Canadian Standards Association: Canadian Standards Association
Listed: File No. LR50900
Canadian Underwriters Laboratories, Inc. Listed: File No. LR50900
Underwriters Laboratories, Inc. Component Recognized File:
MP1502, Vol. 11, Sec. 1
UL Listed: Guide Y10Z
FAN
SWITCH
FAN MOTOR
DAMPER
EXHAUST
DAMPER
OPERATOR
RP418 OR
RP818
SUPPLY
AIR
VOLTAGE
SUPPLY
M5429B
1
2
3
M5428
DEENERGIZED:
PORTS 2 AND
3 CONNECTED,
PORT 1 BLOCKED.
ENERGIZED:
PORTS 1 AND
3 CONNECTED,
PORT 2 BLOCKED.
3
1
2
2
3
1
Product Number Mounting
Voltage rating
at 50 Hz
Voltage rating
at 60 Hz Frequency Electrical Connections Includes
RP418A1008 Surface 208 Vac 50 Hz Junction Box and 15 in. (380 mm) leads Junction Box
RP418A1057 Surface 120 Vac 50 Hz Junction Box and 15 in. (380 mm) leads Junction Box
RP418A1065 Surface 440 Vac 480 Vac 50 Hz; 60 Hz Junction Box and 15 in. (380 mm) leads Junction Box
RP418A1073 Surface 277 Vac 60 Hz Junction Box and 15 in. (380 mm) leads Junction Box
RP418A1081 Surface 208 Vac 60 Hz Junction Box and 15 in. (380 mm) leads Junction Box
RP418A1099 Surface 220 Vac 240 Vac 50 Hz; 60 Hz Junction Box and 15 in. (380 mm) leads Junction Box
RP418A1107 Surface 110 Vac 120 Vac 50 Hz; 60 Hz Junction Box and 15 in. (380 mm) leads Junction Box
RP418B1014 Panel mount 208 Vac 50 Hz 15 in. (380 mm) leads
RP418B1022 Panel mount 240 Vac 50 Hz 15 in. (380 mm) leads
RP418B1030 Panel mount 120 Vac 50 Hz 15 in. (380 mm) leads
RP418B1048 Panel mount 440 Vac 480 Vac 50 Hz; 60 Hz 15 in. (380 mm) leads
RP418B1055 Panel mount 208 Vac 60 Hz 15 in. (380 mm) leads
RP418B1071 Panel mount 110 Vac 120 Vac 50 Hz; 60 Hz 15 in. (380 mm) leads
RP818A1004 Surface 24 Vac 60 Hz Junction Box and 15 in. (380 mm) leads Junction Box
RP818B1002 Panel mount 24 Vac 60 Hz 15 in. (380 mm) leads
RP818B1010 Panel mount 24 Vac 50 Hz 15 in. (380 mm) leads