Air Supply Equipment
70-6925 131
Humidistats 
and 
Thermostats Controllers Sensors Relays Switches Actuators Valves Accessories
Engineering 
Guide
Cross 
Reference
outdoor air is available. After the air is compressed, cooling and 
settling actions in the tank condense some of the excess 
moisture and allow fallout of the larger oil droplets generated by 
the compressor pump.
A high pressure safety relief valve which opens on excessively 
high tank pressures is also required. A hand valve or automatic 
trap periodically blows off any accumulated moisture, oil 
residue, or other impurities that collect in the bottom of the tank.
Air Drying Techniques
General
Air should be dry enough to prevent condensation. 
Condensation causes corrosion that can block orifices and 
valve mechanisms. In addition, dry air improves the ability of 
filters to remove oil and dirt.
Moisture in compressed air is removed by increasing pressure, 
decreasing temperature, or both. When air is compressed and 
cooled below its saturation point, moisture condenses. Draining 
the condensate from the storage tank causes some drying of 
the air supply, but an air dryer is often required.
An air dryer is selected according to the amount of moisture in 
the air and the lowest temperature to which an air line will be 
exposed. For a chart showing temperature and moisture 
content relationships at various air pressures, refer to the 
General Engineering Data section.
Dry Air Requirement
The coldest ambient temperature to which tubing is exposed is 
the criterion for required dryness, or dew point. Dew point is the 
temperature at which moisture starts to condense out of the air.
The coldest winter exposure is normally a function of outdoor 
air temperature. Summer exposure is normally a function of 
temperature in cold air ducts or air conditioned space. The 
typical coldest winter application is an air line and control device 
(e.g., damper actuator) mounted on a rooftop air handling unit 
and exposed to outdoor air temperatures (Fig. 12). The second 
coldest winter exposure is an air line run in a furred ceiling or 
outside wall.
Fig. 12. Winter Dew Point Requirement.
A typical summer minimum dew point application is a cold air 
plenum. Figure 13 shows a 50F plenum application along with 
winter requirements for a year-round composite.
Fig. 13. Twelve-Month Composite 
Dew Point Requirement.
CONDENSING DRYING
The two methods of condensing drying are high-pressure 
drying and refrigerant drying.
High-Pressure Drying
High-pressure drying may be used when main air piping is kept 
away from outside walls and chilling equipment. During 
compression and cooling to ambient temperatures, air gives up 
moisture which then collects in the bottom of the storage tank. 
The higher the tank pressure, the greater the amount of 
moisture that condenses. Maintaining a high pressure removes 
the maximum amount of moisture. The compressor should 
have a higher operating pressure than is required for air supply 
purposes only. However, higher air pressure requires more 
energy to run the compressor. The tank must include a manual 
drain valve or an automatic trap to continually drain off 
accumulated moisture. With tank pressures of 70 to 90 psi, a 
dew point of approximately 70F at 20 psi can be obtained.
Refrigerant Drying
Lowering air temperature reduces the ability of air to hold water. 
The refrigerated dryer (Fig. 14) is the most common means of 
obtaining dry, compressed air and is available in several 
capacities. It provides the greatest system reliability and 
requires minimal maintenance.
Fig. 14. Typical Refrigerant Dryer Airflow Diagram.
70
60
50
40
30
20
10
0
-10
-10  0  10  20 30 40 50 60 70 80
C1098
OUTDOOR AIR TEMPERATURE (F)
REQUIRED MAXIMUM
DEWPOINT OF MAIN AIR (F)
24
TUBING IN 
FURRED 
CEILING
TUBING AT
OUTDOOR AIR 
TEMPERATURE
50
40
30
20
10
0
-10
-10  0  10  20 30 40 50 60
C1099
OUTDOOR AIR TEMPERATURE (F)
REQUIRED MAXIMUM
DEWPOINT OF MAIN AIR (F)
SUMMER REQUIREMENT
COLD AIR PLENUM
WINTER 
REQUIREMENT
AT OUTDOOR AIR
TEMPERATURE
HOT GAS
BYPASS 
CONTROL
HEAT
EXCHANGER
AIR IN
AIR OUT
REFRIGERANT
LINES
REFRIGERATION
UNIT
CONDENSOR
REFRIGERANT DRYER
C1888