Revision 12 ST 700 SmartLine Pressure Transmitters User’s Manual Page 125
11.2.1 Diagnostic Messages
Transmitter standard diagnostics are reported in the two basic categories listed in Table 4. Problems
detected as critical diagnostics drive the analog output to the programmed burnout level. Problems
detected as non-critical diagnostics may affect performance without driving the analog output to the
programmed burnout level. Informational messages (not listed in Table 4 report various transmitter
status or setting conditions.
The Standard Display is only available on HART transmitters
The Standard Display only displays critical diagnostics (Meter Body
Fault, Electronics Module Fault and Meter Body Communication
Fault). Non-critical diagnostics are not displayed.
11.3 Safety