Revision 13 ST 700 SmartLine Pressure Transmitters User’s Manual Page 33
4.6.5 Lightning Protection
If your transmitter includes the optional lightning protection, connect a wire from the Earth Ground
Clamp (see Figure 15) to Earth Ground to make the protection effective. Use a size 8 AWG or
(8.37mm
2
) bare or green covered wire for this connection.