Revision 12 ST 700 SmartLine Pressure Transmitters User’s Manual Page 133
Figure 47 ST 700 Basic Transmitter Inline Model Mounted to an
Optional Bracket
7. Loosen the set screw on the outside neck of the transmitter one (1) full turn.
8. Rotate the Electronics housing a maximum of 180
o
left or right from the center to the position
you require, and tighten the set screw using a 4mm metric socket head wrench. See the
following example and Figure 48.
Example: Rotating the electronics housing
Figure 48 ST 700 Basic Transmitter - Rotating the Electronics
Housing
The mounting position of AP models STA725, STA745, STA72S, STA74S and STA77S
becomes critical as the transmitter spans become smaller. A maximum zero shift of
2.5mmHg for these models can result from a mounting position that is rotated 90o from the
vertical. A typical zero-shift of 0.12mmHg or 0.20 inH2O can occur for a five (5)-degree
rotation from the vertical.