Page 132 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 13
12.5.2 Bracket Mounting Procedure for ST 700 Basic Transmitter,
If you are using an optional bracket, start with Step 1. For an existing bracket, start with Step 2.
5. Refer to Figure 46 for position of the bracket on a 2-inch (50.8mm) nominal, 2.38-inch
(60.4mm) actual, horizontal or vertical pipe, and install a “U” bolt around the pipe and
through the holes in the bracket. Secure the bracket with the nuts and lock washers provided.
Figure 46 ST 700 Basic Transmitter Angle Mounting Bracket
Secured to a Horizontal or Vertical Pipe
6. Align the appropriate mounting holes in the transmitter with the holes in the bracket. Use the
bolts and washers provided to secure the transmitter to the bracket; see the following
variations.
Table 30 ST 700 Basic Transmitter - Mounting Bracket procedure
Transmitter Type
Use Hardware
DP with double-ended process heads
and/or remote seals.
Alternate mounting holes in the ends of the
heads.
In-line GP and AP models (STG7xS
and STA7xS)
The smaller “U” bolt provided to attach the
meter body to the bracket. See the
following example.
Dual-head GP and AP
Mounting holes in the end of the process
head.
Example: Inline model mounted to an optional angle bracket. See Figure 47.