Revision 12 ST 700 SmartLine Pressure Transmitters User’s Manual Page 175
Screen3
Pressure
Custom Unit
[59PCUNIT]
When “Custom” selected for
Screen3 Pressure Units, enter
the custom unit name.
Character string of pressure
custom unit text for display
x = any Alphanumeric value
Press to
enter menu
selection
to select
alphanumeric
character.
to enter
and shift to
the next
character to
the right
Screen3
Pressure
Scaling Low
[60PSCLLO]
When “Custom” selected for
Screen3 Pressure Units, enter
the Screen3 Pressure Scaling
Low value.
Value of the pressure custom
engineering unit corresponding
to the LRV of the transmitter
The limits are:
-999999 to 999999
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right.
Screen3
Pressure
Scaling High
[61PSCLHI]
When “Custom” selected for
Screen3 Pressure Units, enter
the Screen3 Pressure Scaling
High value.
Value of the pressure custom
engineering unit corresponding
to the URV of the transmitter
The limits are:
-999999 to 999999
Press to
enter menu
selection.
Menu to
select
number.
to enter
and shift to
the next digit
to the right.
Screen4 PV
Selection
[62SCRN4]
Display PV
enumerations:
5- None
6- PRESSURE
7- % OUT
8- LOOPOUT
9- FLOW
Select Process Variable (PV)
to be shown on the display
from list.
Press to
enter menu
selection.
Menu to
select from
list
to enter