22 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C  12/06/2005 
System Overview Addressable Modules
2.6  Addressable Modules 
Control Modules and Monitor Modules provide an interface between the control panel and 
conventional notification and initiating devices. Each module can be set to respond to an address 
with built-in rotary switches.  FlashScan-mode devices can select up to 159 addresses; CLIP mode 
devices can select up to 99 addresses.  An LED will blink on a monitor module to indicate 
communication between the module and the control panel.
Monitor and Zone Interface Modules - XLS-MM-A (FlashScan), TC809A1059 (CLIP), 
TC809A1067CDN  (Canadian CLIP), XLS-MM-Z (FlashScan), TC841A1000 (CLIP; 
TC841A1000CDN Canadian) & XLS-MM-D (FlashScan), TC809D1004 (CLIP; 
TC809D1004CDN Canadian) Addressable monitor modules for monitoring conventional 
initiating devices. The XLS-MM-A and TC809A1059 are used for normally open contact alarm 
initiating devices, such as manual pull stations, four-wire smoke detectors, heat detectors, 
waterflow, and supervisory devices. Use the XLS-MM-Z/TC841A1000 for interface to two-wire 
smoke detectors in addition to normally open contacts. The XLS-MM-D and TC809D1004 provide 
two independent 2-wire Initiating Device Circuits (IDCs) at two separate, consecutive addresses. 
Wire supervised IDCs as NFPA Style B (Class B) or Style D (Class A) circuits. The modules come 
with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box. 
Monitor Module - XLS-MM-B/TC809B1008 (TC809B1016CDN Canadian) An 
addressable module that is functionally similar to the XLS-MM-A/TC809A1059 Monitor 
Modules—but offered in a smaller package for mounting directly in the electrical box of the device 
being monitored. (Class B input circuit only.)
Control Module, NAC - XLS-CM-N (FlashScan), TC810N1013 (CLIP, TC810N1013CDN 
Canadian)  Addressable Control Module used as Notification Appliance Circuits (NACs) to 
power and supervise compatible, UL-listed notification appliances. Wired supervised NACs as 
NFPA Style Y (Class B) or Style Z (Class A). The modules come with a thermoplastic cover for 
mounting to a 4-inch (10.16 cm) square mounting box.
Control Module, Relay - XLS-CM-R (FlashScan), TC810R1024 (CLIP, 
TC810R1024CDN Canadian)  Similar to the XLS-CM-N/TC810N1013 except used as a 
Form-C control relay module.
Fault Isolator Module - TC811A-1006  (TC811A1014 Canadian) This module is not 
addressable, but listed here due to its use in an SLC. Protects the system against wire-to-wire short 
circuits on the SLC. It should be placed between groups of sensors in a Style 6 or Style 7 SLC to 
isolate short- and open-circuit problems and protect the rest of the loop so it can continue to operate 
normally.
Pull Station - XLS-MPS (FlashScan) / S464G1007 (CLIP)  An addressable manual pull 
station with key-lock reset feature. The addressable module is housed within the pull station.
 Quad Intelligent Audio Transponder - XPIQ  The XPIQ is an integrated audio amplification 
and distribution subsystem that can direct up to four low-level audio signals through four audio 
amplifiers to integrated, continuously supervised speaker circuits. An on-board power supply 
charges and supervises battery backup.
Multi-Input/Output Modules - XP6-C (XP6-CA Canadian), XP6-R, XP10-M (XP10-MA 
Canadian), XP6-MA (XP6-MAA Canadian)
 FlashScan capable multi-input/output modules are 
available for use on the SLC loop. All are FlashScan capable.  
• XP6-C controls six NAC or speaker/telephone circuits. For more information see the XP6-C 
Installation Document. (Not listed for use in releasing applications.) 
• XP6-R controls six Form-C relays. 
NOTE: For a list of approved notification and initiating devices, refer to the Device Compatibility 
Document.