EasyManuals Logo

Honeywell XLS140 User Manual

Honeywell XLS140
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #60 background imageLoading...
Page #60 background image
60 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
Applications NFPA 72-1999 Central or Remote Station Fire Alarm System (Protected Premises Unit)
4.2 NFPA 72-1999 Central or Remote Station Fire Alarm
System (Protected Premises Unit)
Figure 4.1 shows typical wiring diagram for a NFPA 72-1999 Central Station Fire Alarm System
(Protected Premises Unit) or a Remote Station Fire Alarm System (Protected Premises Unit) using
the Universal Digital Alarm Communicator/Transmitter (UDACT) and control panel. This
provides typical wiring only; connect and program the UDACT according to the directions given in
the UDACT Instruction Manual.
NOTE: An NFPA 72-1999 Central Station requires 24 hours of standby power; an
NFPA 72-1999 Remote Station requires 60 hours of standby power.
NOTE: This application can also be done with the TM-4 Transmitter; refer to the Transmitter
Module TM-4 document for more details.
TB13
EIA-485
+ ACS –
24V NONRST 24V RESET
+ – +
TB7
UDACT in ABS-8R
(shown with cover removed)
Solid earth
ground
To supervised
phone lines
Ferrite cores
P/N 29090
FACP Cabinet
EIA-485
(ACS Mode)
24 VDC
Nonresettable power
Supervised and power-limited
EIA-485 and power wiring
nfs640-udact.cdr
Figure 4.1 Typical Wiring Diagram for a Central Station Fire Alarm System
NOTE: Install a UL-listed 120 ohm End-of-Line resistor (P/N 71244) UDACT TB1 terminals 3
and 4 if this is the last or only device on EIA-485 line.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XLS140 and is the answer not in the manual?

Honeywell XLS140 Specifications

General IconGeneral
BrandHoneywell
ModelXLS140
CategoryFire Alarms
LanguageEnglish

Related product manuals