UPS installation 31
You can install an optional REPO circuit that shuts down the entire parallel system using a single switch. To
install a REPO switch for a parallel system, the selected REPO command (NO or NC) contacts from each UPS
in the system must be in parallel.
To install a REPO switch for a parallel system:
1. Verify that the UPS system is powered down and all power sources are removed. For more information,
see "Powering down the parallel system (on page 73)."
2. Mount the remote REPO switch. HP recommends mounting the REPO switch near the operator's
consoles or near the exit doors. For enclosure dimensions and wiring knockouts, see the REPO switch
manufacturer's installation instructions.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP R1500 - UPS XR and is the answer not in the manual?

HP R1500 - UPS XR Specifications

General IconGeneral
TopologyLine Interactive
Input ConnectionIEC 320 C14
Battery TypeSealed Lead Acid (SLA)
Form FactorRackmount
Nominal Output Voltage230V
Nominal Input Voltage230V
Input Frequency50/60 Hz
Typical Backup Time at Full Load5 minutes
Transfer Time4-8 ms
Hold-up Time10 ms
Input Voltage Range160 - 286 VAC
Interface PortUSB
Battery Recharge Time3 hours
Communication PortsUSB
WaveformSine wave