Appendix A Parameters Shenzhen Hpmont Technology Co., Ltd.
- 114 - HD3N Series User Manual V1.1
Function
Setting Range Default
Unit
Attribute Setting
F00.11 Command setting channel
0: Keypad
1: Terminal
2: SCI
0 1
×
F00.12 M key function
0: Switch running direction
1: Switch local and remote control
2: M key invalid
Valid when LED keypad adopted only
2 1
○
F00.13
Starting frequency digital
setting
0.00 - upper limit frequency 50.00Hz 0.01Hz
○
F00.14 Frequency setting control
Unit: Save selection of frequency
setting at power outage
0: Do not save at power outage
1: Save at power outage
Ten: Control selection of frequency
setting at stop
0: Set frequency is kept in stop
1: Restore to F00.13 at stop
Hundred: Save selection of
communication setting frequency
0: Do not save when power is off
1: Save to F00.13 when power is off
Thousand: Save selection of
frequency setting when switching
frequency source
0: Do nto save
1: Save
1001 1
○
F00.15
Jog running frequency
digital setting 1
0.00 - upper limit frequency 5.00Hz 0.01Hz
○
F00.16 Interval of jog running 0.0 - 100.0s 0.0s 0.1s
×
F00.17 Running direction
0: The same as running command
1: Opposite to running command
0 1
×
F00.18 Reverse
0: Permitted
1: Prohibitted
0 1
×
F00.19
Dead time of direction
switch
0.0 - 3600.0s 0.0s 0.1s
×
F00.20
Enable key operation of
keypad
0: Enable
1: Invalid
Valid when LED keypad adopted only
0 1
○
F00.21 Dormant function
0: Disabled
1: Enable
0 1
×
F00.22 Dormancy wake up time 0.0 - 6000.0s 1.0s 0.1s
○
F00.24 Dormancy delay time 0.0 - 6000.0s 1.0s 0.1s
○
F00.25 Dormancy frequency 0.00Hz - F00.08 0.00Hz 0.01Hz
○