Prerequisites
Tools: protective gloves, step ladder, Phillips screwdriver
Material: spare smoke detector
Document: re extinguishing device layout diagram (standard)
Skill requirement:
re engineer
NO TE
Before replacing the smoke detector, inform the related administration department of the
temporary downtime of the re extinguishing system. After the replacement, inform the
administration department that the system has become operational.
Procedure
Step 1 Switch
o the active and standby power supplies to the re alarm control panel.
Step 2 Hold the smoke detector by hand, and rotate it counterclockwise to remove it
from the base.
Figure 4-65 Removing a smoke detector
Step 3 Remove cables from the base using a Phillips screwdriver.
Step 4 Remove the screws on the base using a Phillips screwdriver, and remove the base.
Step 5 Install the new base in the same position, and reconnect the cables.
Step 6 Hold the smoke detector body, align the smoke detector indicator with the
position shown by (1) in Figure 4-66, and turn the detector body clockwise to the
position shown by (2) in Figure 4-66 to install the smoke detector.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement