Device Method Check Standard Troubleshooting
Hand-held
re
extinguisher
Check the re
extinguisher.
The re
extinguisher is
intact.
Replace the re extinguisher.
The pressure
pointer of the
re extinguisher
is in the green
zone.
Replace the re extinguisher.
The re
extinguisher is
within the
validity period.
Replace the re extinguisher.
Fire control
cable
Check cables
connected to the
electromagnetic
valve and pressure
announciator.
Cables are
securely
connected to the
electromagnetic
valve and
pressure
announciator.
Connect the cable properly.
Emergency
start/abort
switch
Check the emergency
start/abort switch.
The exterior and
key panel are
intact. The run
indicator is
steady green.
If the exterior is damaged, replace the
emergency start/abort switch.
3.5.4 Fire Extinguishing System (CE)
Table 3-12 Quarterly maintenance checklist for the re extinguishing system
Device
Method Check Standard Maintenance Guide
Extinguishant
control panel
batteries
1. Switch o the power
input circuit breaker of
the re alarm control
panel so that the
batteries power the
panel.
2. Measure the battery
voltage using a
multimeter.
1. The extinguishant
control panel reports
a power supply fault.
2. The battery voltage is
24±1 V DC.
Replace the extinguishant
control panel batteries.
Hand-held
re
extinguisher
Check the hand-held re
extinguisher.
The hand-held re
extinguisher is in good
condition.
Replace the hand-held
re extinguisher.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 3 Routine Maintenance
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 39