Item Method Check Standard Troubleshooting
Check whether the
ambient
temperature,
humidity, and solar
radiation outside the
prefab. module meet
requirements.
The external temperature,
humidity, and solar
radiation requirements of
the FusionDC1000 are as
follows:
● Temperature:
– Normal temperature:
–20°C to +55°C
– Low temperature: –
40°C to +45°C
● Humidity: 5%–95% RH
● Solar radiation: ≤ 1120
W/m
2
For details, contact Huawei
technical support.
3.5 Quarterly Maintenance
3.5.1 Power Supply and Distribution System
Table 3-9 Quarterly maintenance checklist for the power supply and distribution system
Device
Method Check Standard Maintenance Guide
SmartLi Battery module
appearance
The battery modules are
clean.
Clean the battery
modules using dry cotton
cloth. Exercise caution
when cleaning a battery
module because its
voltage is high.
Connections Each terminal is securely
connected.
Check the bolt at every
terminal. If any bolt is
loose, tighten it.
3.5.2 Monitoring System
Table 3-10 Quarterly maintenance checklist for the monitoring system
Check Item
Operation Check Standard Troubleshooting
Access
actuator
Power input Input voltage: 36–60 V DC Check the input power
cables if the input voltage
is abnormal.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 3 Routine Maintenance
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 35