After the wiring terminals are disconnected from the electrical actuator, the extinguishant
control panel generates an alarm, which is normal.
2. Press the manual gas release button on the extinguishant control panel.
That the horn strobe is triggered indicates that the horn strobe works properly.
3. Reset the manual gas release button.
4. Flip the key Enable Control counterclockwise (rightward). Reset the
extinguishant control panel by pressing Reset on it. Then, reset the key
Enable Control clockwise (leftward).
----End
4.5.6 Replacing a Fire Alarm Bell (CE)
Prerequisites
A spare
re alarm bell of the same model is available and functional.
Impact on the System
The
re extinguishing system stops working during the replacement.
Preparations
Tools: hex key, Phillips screwdriver, protective gloves, step ladder
Materials: spare
re alarm bell
Documents: re extinguishing drawings and parameters
Skill requirement:
re engineer
Before replacing the re alarm bell, inform the related administrative departments
of the temporary downtime of the re extinguishing system. After the
replacement, inform the administration department that the system has become
operational.
Procedure
Step 1 Disconnect the battery cables, and switch o the input circuit breaker of the
extinguishant control panel.
Step 2 Remove screws securing the
re alarm bell using a hex key, and remove the cover.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 153