Step 5 Install the new re alarm sounder.
Step 6 Switch on the active and standby power supplies to the re alarm control panel.
Step 7 Check that the new re alarm sounder is working properly.
Unlock the re alarm control panel, and press the ALARM BELL key to trigger the re alarm
sounder.
----End
Follow-up Procedure
Dispose of the removed
re alarm sounder that is conrmed faulty.
4.4.9 Replacing the Emergency Start/Abort Switch
Prerequisites
A spare emergency start/abort switch of the same model is available and
functional.
Impact on the System
The
re extinguishing system stops working during the replacement.
Prerequisites
Tools: Phillips screwdriver,
at-head screwdriver, protective gloves
Material: spare emergency start/abort switch
Document:
re extinguishing device layout diagram (standard)
Skill requirement:
re engineer
Before replacing the emergency start/abort switch, inform the related administration
department of the temporary downtime of the re extinguishing system. After the
replacement, inform the administration department that the system has become
operational.
Procedure
Step 1 Switch o the active and standby power supplies to the re alarm control panel.
Step 2 Use a Phillips screwdriver to remove the screws from the emergency start/abort
switch, as shown in Figure 4-76.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 131