3.4.1 Power Supply and Distribution System
Table 3-3 Monthly maintenance checklist for the power supply and distribution system
Maintenanc
e Item
Method Check Standard Troubleshooting
Integrated
UPS
Operating
environment
Ambient
temperature:
0–40°C
Humidity:
5%–95% RH
(non-
condensing)
Rodent-proof
measures
have been
taken for the
equipment
room.
The
equipment
room is
airtight.
If the humidity or temperature is
abnormal, check the smart cooling
product status.
Put rodent-proof bae plates at the
door of the UPS equipment room.
Check that the equipment room is
airtight and not in a direct
ventilation environment.
Power grid
environment
Input voltage:
380 V AC,
400 V AC, or
415 V AC
(line voltage)
Output
voltage: 380
V AC, 400 V
AC, or 415 V
AC (tolerance
± 1%, line
voltage)
Frequency:
40–70 Hz
If the input voltage is abnormal,
check the power grid status and
input cable connection.
If the output voltage is abnormal,
check the UPS running status and
check whether an alarm is
generated.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 3 Routine Maintenance
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 27