4.4 Replacing Fire Extinguishing System Components
(Standard)
4.4.1 Changing an Address Code
Prerequisites
Before replacing a re extinguishing device, reset the address code for the device.
Procedure
1. Press and hold the ON/OFF key on the encoder for 1 second to start the
encoder.
2. Press # to switch the mode. When 324 is displayed on the screen, use a
dedicated external connection cable to connect the terminal device and set
the address code for the device on the bus.
NO TE
The encoding indicator is steady on. Press the number keys to enter the address
code to be encoded, and then press the Run/Stop key to encode the address code.
After the encoding is successful, the address code is displayed on the screen, and
the buzzer sounds once.
If the encoding fails, the screen blinks , and the buzzer sounds three times.
In this case, check that the cable connection and terminal type are correct, and
then perform the encoding again.
If an incorrect address is entered, press Delete to delete the address and enter the
address to be encoded again.
3. On the screen of the re alarm control panel, choose Operation > Auto
Login to register the preset address code in the
re alarm control panel.
4. Choose Bus Setting > Detector/Module Setting. Check that the device type
of the gas release indicator, re alarm horn/strobe, and input/output module
corresponds to gas release indicator, indoor
re alarm horn/strobe, and
outdoor re alarm horn/strobe respectively. If not, select the correct device
type from the drop-down list.
4.4.2 Replacing a Smoke Detector
Prerequisites
A spare smoke detector of the same model is available and functional.
Impact on the System
The
re extinguishing system stops working during the replacement.