NO TICE
Before replacing the re alarm sounder, inform the related administration
department of the temporary downtime of the re extinguishing system. After the
replacement, inform the administration department that the system has become
operational.
Procedure
Step 1 Switch o the active and standby power supplies to the re alarm control panel.
Step 2 Push the re alarm sounder out of the base.
Figure 4-74 Removing the
re alarm sounder
Step 3 Cut o the power cable of the re alarm sounder, as shown in Figure 4-75.
Figure 4-75 Cutting o the power cable
Step 4 Connect the input wires with the two wires (polarity insensitive) of the spare re
alarm sounder and wrap the connection points using insulation tape.
NO TE
Cord end terminals are recommended if applicable.