Skill requirement: re engineer
NO TICE
Before replacing the extinguishant control panel, inform the related administrative
departments of the temporary downtime of the
re extinguishing system. After
the replacement, inform the administration department that the system has
become operational.
Procedure
Step 1 Switch o the input circuit breaker on the extinguishant control panel.
Step 2 Remove the cables from the battery, and take out the battery.
Step 3 Remove all cables connected to the terminals on the extinguishant control panel.
NO TE
While removing the cables, label the cables with their corresponding port numbers for later
connection.
Step 4 Remove the corrugated pipes and cables from the extinguishant box.
Step 5 Remove the screws using a Phillips screwdriver, and take out the faulty
extinguishant control panel.
Figure 4-114 Removing the extinguishant control panel
Step 6 Install the new extinguishant control panel in the same position.
Step 7 Put the corrugated pipes and cables back to the box, and reconnect the cables
according to labels.
Step 8 Put the batteries to the same position.
Step 9 Switch on the input circuit breaker of the extinguishant control panel, and connect
the battery cables.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement