Reclaim or dispose of the refrigerant in accordance with local laws and
regulations. Do not discharge the refrigerant to the atmosphere. During the
reclaim process, the R410A refrigerant composition may change. Therefore, you
are not advised to
rell the reclaimed R410A refrigerant to the cooling system.
1. Prepare a pressure gauge with two hoses, connect one hose to the outdoor
unit needle valve 10 minutes after the smart cooling product has been shut
down, and connect the other hose to nearby sheet metal, such as a smart
cooling product supportive leg or support.
Figure 4-13 Discharging refrigerant
– Bind the rubber hose to the sheet metal adjacent to the outdoor unit needle valve.
– The hose should be bound at a position close to the hose outlet to a tension not
squeezing the hose.
2. Slowly open the valve on the pressure gauge to start discharging refrigerant.
When discharging the refrigerant, verify that refrigerant oil does not ow out of the
hose. If a small amount of refrigerant oil continually ows out of the hose, place a
vessel or rag under the hose to catch the refrigerant oil.
3. Keep the pressure gauge valve open after the refrigerant draining slows down
after a period of time until no refrigerant is obviously
owing out.
4. Wear anti-freezing gloves and press the needle valves on the smart cooling
product indoor unit to check whether refrigerant ows out.
– If refrigerant ows out, perform Step 10.1–Step 10.3 on the
corresponding needle valve.
– If no refrigerant ows out, go to Step 10.5.