Figure 4-57 Connecting input power cables to the PDU
----End
4.3.2.3 Connecting rPDU Power Cables
Context
The rPDU complying with China standards or IEC can be congured based on site
requirements.
If the rPDU is not
congured with industrial connectors, connect the rPDU cables.
Procedure
Step 1 Connect cabinet rPDU power cables.
1. Remove the front panel from the rPDU.
2. Connect one end of the reserved rPDU power cable to the rPDU terminal
block and the other end to the power distribution subrack.
FusionModule500 Smart Mini Data Center
User Manual 4 Installation Guide
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 101