3.3.1 Application Conditions
Operating Environment
Table 3-6 Operating environment
Item Integrated air conditioner
Operating temperature 0–40°C
Operating humidity 5%–95% RH (non-condensing)
Storage temperature –40°C to +70°C (without refrigerant)
–40°C to +55°C (with refrigerant)
Storage humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m, derated at above 1000 m For details
about derating coecients, see Table 3-7.
Table 3-7 Derating coecients
Altitude
(m)
0 1000 1500 2000 2500 3000 3500 4000
Air
volume
coecie
nt
1 0.887 0.835 0.785 0.737 0.692 0.649 0.608
Cooling
capacity
coecie
nt
1 0.940 0.909 0.878 0.846 0.815 0.784 0.753
3.3.2 Technical Specications
Table 3-8 Technical specications
Item
Integrated Air Conditioner
Power system 220–240 V AC 50/60 Hz, 1 Ph
Refrigerant R410A
Cooling capacity
3.5 kW
a
Air supply mode Upward air supply and return at the indoor side,
and rear air return at the outdoor side
FusionModule500 Smart Mini Data Center