A ground terminal is greater than or equal to M8 in dimensions. A yellow
ground label is attached close to the general ground terminal for
cabinets.
Connect equipotential cables to metal components without carrying currents
in the module, such as metal doors and windows. Each equipotential cable
has a minimum cross-sectional area of 6 mm
2
.
3.7 Cable Management
The cable tray is used to manage cables in the cabinet. The cable tray is used to
route cables from the front of the cabinet to the rear of the cabinet.
Cable Tray
A cable tray is used for forward and backward cabling. It uses mounting ears to
facilitate device installation.
Figure 3-22 Cable tray
Table 3-38 Cable tray technical specications
Dimensions (H x W x
D)
Weight Space Occupied
43.6 mm x 482.6 mm x
250 mm
1.89 kg 1 U
FusionModule500 Smart Mini Data Center
User Manual 3 System Architecture
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 54